Electrical Parameter | Mechanical Parameter | ||
Frequency | 50/60Hz | Case | PC/UL94-V0 |
Rated Input | 300A-600A | Bobbin | PA66 |
Measuring range | 5%In-120%In | Core | Silicon steel |
Rated Output | 40mA,50mA,60mA,100mA,0.333V | Construction | Screw |
Ratio Voltage | 0.72KV (AC) | Operating Temp | -25℃~+75℃ |
Dielectric strength | 3.0KV/1mA/1min | Operating Humidity | ≤85% |
Insulation Resistance | DC500V/100MΩ min | Output Connection | Terminal |
説明
Introduce:
HACT series provide precision measurement for energy monitoring applications to sensing power loading equipment without interrupting the lines. It has been specifically designed to be easy to open and yet maintain the accuracy required for intelligent meters, quick to fit around cables.
Features:
Reliable locking mechanism.
Ergonomic design.
Network equipment.
Measurement instruments.
Applications:
Energy and sub-metering products.
Electrical load monitoring.
Network equipment.
Measurement instruments.
Tecnial data
MODEL | HACT | ||||
Current Ratio | 300A/100mA | 400A/40mA | 500A/50mA | 600A/60mA | 300~600/0.333V |
Primary Current(A) | 300A | 400A | 400A | 600A | 300A~600a |
Max. Current(A) | 360 | 480 | 600 | 720 | 720 |
Secondary Current(mA) | 100mA | 40mA | 50mA | 60mA | 0.333V |
Load Resistance(Ω) | 50Ω | 50Ω | 50Ω | 50Ω | / |
Class | 0.5/1.0 | 0.5/1.0 | 0.5/1.0 | 0.5/1.0 | 0.5/1.0 |
Turns Ratio | 125.0006944 | 10000:1 | 10000:1 | 10000:1 | / |
Protection Level | 7.5V0-P | 7.5V0-P | 7.5V0-P | 7.5V0-P | |
Insullation Category | CATⅢ | ||||
Operating Condition | -20℃~+50℃,≤85%RH,No condensation,IN-house&Any direction installable | ||||
Storage Condition | -30℃~+50℃,≤85%RH,No condensation |